4 walktest, Walktest – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 142

Advertising
background image

142

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Programming

Maintenance Programming Level

Pressing 2 while viewing the Program Check screen will display a screen similar to the following:

The Zone No Input screen allows the programmer to view the zones which have not been pro-
grammed to at least one input device (not including general alarm Zone 00). The example in the
preceding screen indicates that Zones 05, 07, 09, 10, and 11 have been programmed to an address-
able module (control module in this example) with an address of 001 on loop 1 but have not been
programmed to any input devices. Use the up and down arrow keys to view all the zones without
input assignments.

Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be
displayed:

The Zone No Output feature allows the programmer to view the zones which have not been pro-
grammed to at least one output device (not including general alarm Zone 00). The example in the
preceding screen indicates that Zones 05, 07, 09, 10, and 11 have been programmed to an address-
able detector with an address of 001 on loop 1 but have not been programmed to any output
devices. Use the up and down arrow keys to view all the zones without output assignments.

3.7.4 Walktest

To perform a walktest, press 1 while viewing Maintenance Screen #2. The following screen will be
displayed:

The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. The dis-
play will read UNIT IN WALKTEST. To end the Walktest, press the Esc (Escape) key.

Pressing 3 after the walktest has been completed, will allow the operator to view the results of the
walktest.

ZONES NO INPUT

05 07 09 10 11 1M001

ZONES NO OUTPUT

05 07 09 10 11 1D001

PROGRAMMING

1=WALKTEST

2=SYSTEM

3=ZONE SETUP

Maintenance Screen #2

WALKTEST

1=SILENT

2=AUDIBLE

3=VIEW RESULT

Walktest Screen