MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Programming

Master Programming Level

The following screens will be displayed for either selection:

Enabled

Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will
prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key
will cause the display to toggle between Enabled Yes and Enabled No.

NAC #

1=ENABLED YES

2=TYPE BELL

3=SILENCEABLE YES

NAC Screen #1

NAC #

1=ZONE

00 00 00 00 00

2=SIL INHIBITED NO

NAC Screen #2

NAC #

1=AUTO SILENCE 00

2=CODING

TEMPORAL

NAC Screen #3

NAC #

1=SYNC TYPE S

NAC Screen #4