Programming

Master Programming Level

Pressing 3 while viewing Programming Screen #3 will display the following screen:

Note that PR4800 in the display indicates that a supervised printer, configured for 4800 baud, has
been previously programmed into the system.

Annunciators/UDACT

Pressing 1 while viewing the Options Screen will cause the control panel to display the following
screens:

A Terminal Mode annunciator, ACS Mode annunciator or ANN-BUS annunciator/module can be
installed in the system. Do not use a mix of ACS annunciators and ANN annunciators since they
use different communication protocols. ACS or ANN annunciators use the same TB6 terminal
block connection. To install any of these devices, press the number corresponding to the desired
device shown in the Annunciator Screen.

Term Options

While viewing the Annunciators Screen, each press of the 1 key for Term Options, will cause the
display to toggle between Term Enabled No and Term Enabled Yes.

OPTION MODULES

1=ANNUNCIATORS/UDACT

2=ONBOARD DACT

3=PRINTER/PC PR4800

Options Screen

ANNUNCIATORS

1=TERM ENABLED NO

2=ACS OPTIONS

3=ANN-BUS OPTIONS

Annunciator Screen

NOTE: The LCD-80F is a Terminal Mode annunciator. To enable the FACP for LCD-80F
operation, press 1 for Term Enabled Yes.