Page 78

Advertising
background image

78

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Programming

Master Programming Level

3. With the cursor on the last letter of the Noun field, press the zero key again to increment the

room number to 305.

4. Press the right arrow key to advance the zone field.
5. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01

through Z99 may be selected to link software zones.

Module Programming

Pressing 2, while viewing Point Program Screen #2, will allow the programmer to add, delete or
change the programming of an addressable module. The following screen will be displayed by the
control panel:

Add Module

Pressing 1 while viewing the Modules Screen will display the following screen which allows the
programmer to add a new module address to programming:

A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit module address, such as 005.

When the last digit is keyed-in, the following screen will be displayed:

POINT PROGRAM

SELECT TYPE

1=DETECTOR

2=MODULE

Point Program Screen #2

MODULES

1=ADD

2=DELETE

3=EDIT

Modules Screen

ADD MODULE

ENTER MODULE#

***

Add Module Screen #1

ADD MODULE

1=CONTROL

2=MONITOR

Add Module Screen #2