Ann-bus audio panel control – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 38

Advertising
background image

38

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Product Description

Accessories

ANN-RLY Board Layout and Connection to FACP

Figure 1.15 illustrates the ANN-RLY board showing locations of screw terminals for connection to
the FACP and the DIP switches for selecting the ANN-BUS ID number.

ANN-BUS Audio Panel Control

The FACP is capable of providing automated activation of the ACC-25/50(ZS/T) zoned system
speaker circuits. To do this, the FACP must be enabled to communicate with the ACC-25/50ZS
Audio Panel over the ANN-BUS (refer to “ANN-BUS Enabled” on page 121). This is accom-
plished by programming the Audio Panel ANN-BUS address into the FACP (refer to “Modules
Installed” on page 121).
For details on setting the ANN-BUS address and programming the audio
panel, refer to the ACC-25/50ZS Series Audio Panel manual (document #51889).

The ACC-25/50ZS Series audio panel connects to the FACP via the ACS/ANN-BUS communica-
tion circuit. Zones 33 - 56 on the FACP correspond to the ACC-25/50ZS Series audio circuits
1 - 24. Zone 32 on the FACP serves as the All-Call zone and will activate all audio panel output
circuits. The programmer can select which of the five audio messages at the audio panel will play
when an FACP input zone goes into alarm (refer to “Zone Message” on page 149). The message
will play over the corresponding audio panel output circuit.

Figure 1.15 ANN-RLY Board Layout and Connection to FACP

FACP

ANN-RLY

ANN-BUS

+24 VDC

-24 VDC

Ground Wire
attaches to chassis
(see documentation
supplied with module)

96

00

lst

o

rly.w

m

f

ANN-BUS (ID#)
Address DIP switch

!

WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.

Advertising