Nac type 1=bell 2=horn 3=strobe – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 109

Advertising
background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

109

Master Programming Level

Programming

Type

The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen #1.
The following screen will be displayed. Press the down arrow key to view additional screens:

Select the NAC device type by pressing the number corresponding to the type in the appropriate
screen. When the selection is made, the display will return to NAC Screen #1.

The following table contains NAC type codes and their functions:

Silenceable

Pressing 3 while viewing NAC Screen #1 will cause the display to change to Silenceable No. This
will prevent the selected main circuit board NAC from being silenced by pressing the Alarm
Silence key or by the Auto Silence feature. Each press of the 3 key will cause the display to toggle
between Silenceable Yes and Silenceable No.

Important: When a Notification Appliance Circuit with a mix of audible and visual devices is
programmed for silenceable and the Synced Strobe feature is selected, only the audible devices
will be turned off if the Silence key is pressed. The visual devices (strobes, etc.) will continue to
operate. If the Strobe Sil Sync feature is selected, Silence will turn off both audible and visual
devices.

NAC Type Code

Special Function

Bell

None

Horn

None

Strobe

None

Synced Strobe

Synchronized to manufacturer

Strobe Sil Sync

Same as Synced Strobe but Silence turns off audible & visual devices

Future Use

None

Future Use

None

Future Use

None

Blank

None

NAC #

1=ENABLED

2=TYPE

3=SILENCEABLE

NAC Screen #1

NAC TYPE

1=BELL

2=HORN

3=STROBE

Type Screen #1