Master Programming Level

Pressing the down arrow key will display additional detector types as indicated in the following
table:

While viewing any Detector Type screen, select the type of detector being programmed by pressing
the corresponding keyboard number key. The display will return to Edit Detector Screen #2 and
indicate the selection next to the Type option.

Verification

Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and
not a false alarm. This feature is selected by pressing 3 while viewing the Edit Detector Screen #2
so that the display reads Verification On. Each time the 3 key is pressed, the display will toggle
between Verification On and Verification Off. For a detailed description, refer to “Alarm Verifica-
tion” on page 159.

Walktest

The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable a device for the Walktest feature,
press 1 while viewing the Edit Detector Screen #3 until the display reads Walktest Yes. Each press
of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to “Walk-
test” on page 160.

PAS

The PAS (Positive Alarm Sequence) option will program the detector to delay panel activation
(including alarm relay and communicator) for a period of 15 seconds plus a programmable time of
up to 3 minutes. Zone 97, however, will activate immediately and may be used to connect a signal-
ing device to indicate PAS activation (do not use a Notification Appliance Circuit for this purpose).

To enable the PAS feature, press 2 while viewing the Edit Detector Screen #3 until the display reads
PAS Yes. Each press of the 2 key will cause the display to toggle between PAS Yes and PAS No.
Refer to “Positive Alarm Sequence” on page 158.

For example, if a detector with address 005 is to be configured for PAS operation:

• Select PAS Yes when editing the detector set to address 005

Detector Type

Action When Activated

Smoke Photo

Fire Alarm

User-Defined-1

same as previous (Smoke Photo)

Smoke Ion

Fire Alarm

User-Defined-2

same as previous (Smoke Ion)

Heat Detect

Fire Alarm

User-Defined-3

same as previous (Heat Detect)

Smoke DuctP

Fire Alarm

User-Defined-4

same as previous (Smoke DuctP)

Photo w/Heat

Fire Alarm

User-Defined-5

same as previous (Photo w/Heat)

Duct-Superv

Supervisory, latching

User-Defined-6

same as previous (Superv DuctP)

Photo-SupervAR

Supervisory, nonlatching (works only in LiteSpeed)

User-Defined-7

same as previous (Photo-SupervAR)

ADAPT

Fire Alarm

User-Defined-8

same as previous (ADAPT)

Beam

Fire Alarm

User-Defined-9

same as previous (Beam)

NOTE: If a detector is selected as a SUPERV DUCTP type, it will function like a supervisory point,
not a fire alarm point. The supervisory LED and supervisory relay will activate, not the fire alarm LED
or alarm relay, if smoke is sensed.

EDIT DETECTOR

1=WALKTEST

2=PAS

3=PRE-SIGNAL

Edit Detector Screen #3