MBT-1 Municipal Box Trip - Silenceable

C.2 MBT-1 Municipal Box Trip - Silenceable

The following figure illustrates the connection of the MBT-1 (Municipal Box Trip) between the
FACP and a Local Energy Municipal Box. The use of an addressable control module programmed
for General Alarm and Silenceable allows silencing of the Municipal Box without resetting the
panel or box.

FACP

CMF-300

24 VDC, Nonresettable

+ -

SLC Loop B+ -B

Shield

red

black

MBT-1

brown wire

white wire

EOLR-1 Power
Supervision Relay

Alarm polarity shown!

-

+

- To next device
+ on SLC Loop
Braided-shield/Drain Wire

The CMF-300 must be

programmed as Silenceable

and General Alarm.

Gamewell Model

M34-56 Local Energy

Municipal Box

Note: 10

 maximum loop

resistance due to wiring from
power supply to Municipal Box.

Connect wires to two
red terminals on box.

(All contacts shown in energized position)