NFPA Standard-Specific Requirements

NFPA 72 Auxiliary Fire Alarm System

All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.

Notes:

1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2. Cut JP6 on the FACP main circuit board to supervise placement of 4XTMF module and circuit.
3. Cut JP5 on the FACP main circuit board to enable FACP Supervisory relay.
4. Refer to “4XTMF Transmitter Module Installation” on page 55 for detailed information.

Figure C.3 Municipal Box Connected to 4XTMF Transmitter Module

FIRE

Gamewell Model M34-56

Local Energy Municipal Box

Polarities shown in alarm condition

+

Nonpower-limited

Municipal Box Circuit

+

-

-