Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 193

Advertising
background image

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

193

Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts

NFPA Standard-Specific Requirements

C.1 Central Station/Remote Station Transmitter: Connection

to FACP Dry Contacts

The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central
Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central
Station/Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value
determined by the Transmitter manufacturer. Power is also provided by the Central Station/Remote
Station Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter
manufacturer’s manual for details.

Figure C.6 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter

Typical Central Station/Remote Station Transmitter Module

Typical Input Zone Triggers

FACP Main Circuit Board

Al

arm

T

rouble*

Supervisor

y

*Note: The Trouble Relay is a fail-
safe relay. With power applied to
the FACP and no troubles in the
panel, the wiring should be
connected to the NO and C contacts
as indicated in the illustration.

m

s96

00

ls

dr

yxm

it.w

mf