Master Programming Level

3.6.11 Clear Program

Pressing 2 while viewing Programming Screen #4, will select the Clear Program option. This will
cause the LCD to display the following screens:

Pressing 1, for Whole System while viewing the Clear Program Screen #1, will clear all general
system programming options and all programmed addressable devices from the nonvolatile mem-
ory of the FACP. This function is useful when the control panel is first installed, prior to autopro-
gramming. Note that it is necessary to autoprogram after using the Clear Whole System function.

Pressing 2, for All Loops while viewing the Clear Program Screen #1, will clear all programming
related to all SLC loops and connected addressable devices.

Pressing 3, for Loop 1 while viewing the Clear Program Screen #1, will clear only the program-
ming related to SLC Loop 1 and the connected addressable devices.

Pressing 1, for Loop 2 while viewing the Clear Program Screen #2, will clear only the program-
ming related to SLC Loop 2 and the connected addressable devices.

Before executing any of the Clear commands listed above, the control panel will provide a warning
to the user by prompting with the following display:

Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will pre-
vent programming from being cleared.

PROGRAMMING

1=PASSWORD CHANGE

2=CLEAR PROGRAM

3=PROGRAM CHECK

Programming Screen #4

CLEAR PROGRAM

1=WHOLE SYSTEM

2=ALL LOOPS

3=LOOP1

CLEAR PROGRAM

1=LOOP2

Clear Program Screen #1

Clear Program Screen #2

WARNING!

SYSTEM CHANGE

PROCEED?

1=YES 2=NO