4.

POLYNOMIAL

INPUT 1:

X

PROMPT:

DVxx INPUT X

INPUT 2:

A

PROMPT:

DVxx INPUT A

INPUT 3:

B

PROMPT:

DVxx INPUT B

INPUT 4:

C

PROMPT:

DVxx INPUT C

INPUT 5:

D

PROMPT:

DVxx INPUT D

ACTUATOR:

n/a

RESET:

n/a

OUTPUT:

= A*X**3 + B*X**2 + C*X + D

5.

LINEAR MASS FLOW - AGA 3 LINEAER GAS FLOW

INPUT 1:

F

PROMPT:

DVxx RAW FLOW

INPUT 2:

PRES

PROMPT:

DVxx STATIC PRES ABS

INPUT 3:

TEMPF

PROMPT:

DVxx FLOW TEMP

°

F

INPUT 4:

COMP

PROMPT:

DVxx COMP. CORRECT.

INPUT 5:

C

PROMPT:

DVxx SCALING CONST.

ACTUATOR:

n/a

RESET:

n/a

OUTPUT:

=C*F*SQRT (PRES/(TEMPR*COMP))
where: TMPR = TEMPF + 459.67

If INPUT 1 is "NOT USED", then F=1
If INPUT 2 is "NOT USED", then PRES=1
If INPUT 3 is "NOT USED", then TEMPR=1 (not TEMPF)
If INPUT 4 is "NOT USED", then COMP=1
If INPUT 5 is "NOT USED", then C=1

NOTES:

F - Raw Linear Fow Input
PRES - Static Pressure - must be ABSOLUTE
TEMPF - Flow Temperature - must be degrees F
COMP - Compressibility Correction
C - Scaling Constant

This function converts TEMP from degrees F to degrees R in the equation.

6.

DP MASS FLOW - AGA 3 DP GAS FLOW

INPUT 1:

DP

PROMPT:

DVxx DIFFERENT. PRES

INPUT 2:

PRES

PROMPT:

DVxx STATIC PRES ABS

INPUT 3:

TEMPF

PROMPT:

DVxx FLOW TEMP

°

F

INPUT 4:

COMP

PROMPT:

DVxx COMP. CORRECT.

INPUT 5:

C

PROMPT:

DVxx SCALING CONST.

ACTUATOR:

n/a

RESET:

n/a

OUTPUT:

= C*SQRT ((DP*PRES) / (TEMPR*COMP))
where TEMPR = TEMPF + 459.67)

If INPUT 1 is "NOT USED", then DP=1
If INPUT 2 is "NOT USED", then PRES=1
If INPUT 3 is "NOT USED", then TEMPR=1 (not TEMPF)
If INPUT 4 is "NOT USED", then COMP=1
If INPUT 5 is "NOT USED", then C=1