Section 4

Edition 3
Rev G

4-68

L

E

D

S

&

R

E

L

A

Y
S

4.1.10 RELAYS

Relays only available when specified and present in the model number order matrix.

From the Normal Display, press the

until CONFIGURATION is seen in the lower display line. If PASS-

WORDS appears in the lower display line, the correct "password" will need to be entered before access to Con-

figuration is allowed. If CONFIGURATION is not displayed, then Configuruation has been disabled. Refer to

SEction 9, Enables and Passwords, for instructions to enable Configuration.

With CONFIGURATION in the display, press the

, then the

until RELAYS appears in the lower display

line.

1. Press the

to display RELAY NUMBER.

2. Press the

to advance to the next parameter, RELAY USAGE.

RELAY NUMBER

1

Selections

1 to 8

Press the

to change, then

to

desired number, then press the

.

Press the

to change, then

to

desired choice, then press the

.

RELAY x USAGE

STATE OR ON - OFF

Selections

STATE OR ON-OFF

PULSED OUTPUT

TIME PROPORTIONING