6 voltage connections, Figure 2-9 figure 2-9a – West Control Solutions MRC 9000 User Manual

Page 30

Advertising
background image

Section 2

2-11

Edition 3

Rev G

2.3.6 VOLTAGE CONNECTIONS

Note: Up to four Input Boards may be present; stacked 4 high. Input Board 1 is the bottom board. Two
versions of Input Board s may be found, see Figure 2-9 and Figure 2-9A.

Input Board 1 is used for Input 1 and, if equipped, Input 2. Input Board 2 is used for Input 3 and Input 4, if
equipped. Input Board 3 is for Input 5 and Input 6. Input Board 4 is for Input 7 and Input 8.

Connect positive (+) leg to terminal 1 and negative (-) leg to terminal 2 on the Input Board(s) to be volt input.
Terminal block 1 (TB1) is Input 1, 3,5 and 7 and terminal block 2 (TB2) is Input 2, 4, 6, and 8.

NOTE: INPUT CONDITIONING JUMPERS MUST BE POSITIONED AS SHOWN FOR VOLT INPUT IN EITHER
FIGURE 2-8 OR 2-8A DEPENDING ON WHICH CIRCUIT BOARD IS FITTED. ALSO NOTE: THERE IS NO
SENSOR BREAK DETECTION FOR ZERO BASED VOLT INPUTS. EXAMPLE: 0-5V.

FIGURE 2-9

FIGURE 2-9A

JU1

JU11

U6

JU7

+

+

-

-

1

1

TB1

TB2

JU2

JU5

JU12

JU4

JU8

JU15

JU16

LOW

VOLT

INPUT
SPAN

NARROW

0/25 mV

WIDE

0/100mV

INPUT 2, 4, 6, 8

JU8

INPUT 1, 3, 5, 7

JU7

JU3

0/10V
0/5V

0/1V &mV

JU6

0/10V
0/5V

0/1V &mV

JU3

JU6

NOTE: Terminal Block 1, Terminal 1 is on the RIGHT,
Terminal Block 2, Terminal 1 is on the LEFT.

LOW

VOLT

INPUT
SPAN

NARROW

0/25 mV

WIDE

0/100mV

INPUT 2, 4, 6, 8

JU8

INPUT 1, 3, 5, 7

JU7

JU3

0/10V
0/5V

0/1V &mV

JU6

0/10V
0/5V

0/1V &mV

U1

+

+

-

-

1

1

TB1

TB2

JU5

JU6

JU16

JU7

JU3

JU2

JU15

JU8

Advertising