8 switch input connections – West Control Solutions MRC 9000 User Manual

Page 32

Advertising
background image

Section 2

2-13

Edition 3

Rev G

2.3.8 SWITCH INPUT CONNECTIONS

Note: Up to four Input Boards may be present; stacked 4 high. Input Board 1 is the bottom board. Two
versions of Input Board s may be found, see Figure 2-10 and Figure 2-10A.

Input Board 1 is used for Input 1 and, if equipped, Input 2. Input Board 2 is used for Input 3 and Input 4, if
equipped. Input Board 3 is for Input 5 and Input 6. Input Board 4 is for Input 7 and Input 8.

Connect one leg to terminal 1 and connect the other leg to terminal 2 on the Input Board(s) to be switch input.
Terminal block 1 (TB1) is Input 1, 3, 5, and 7 and terminal block 2 (TB2) is Input 2, 4, 6, and 8.

NOTE: INPUT CONDITIONING JUMPERS MUST BE POSITIONED AS SHOWN FOR SWITCH INPUT IN
EITHER FIGURE 2-8 OR 2-8A DEPENDING ON WHICH CIRCUIT BOARD IS FITTED.

FIGURE 2-11

FIGURE 2-11A

JU3

JU1

JU11

U6

JU7

+

+

-

-

1

1

TB1

TB2

JU2

JU5

JU12

JU4

JU6

JU8

JU15

JU16

NOTE: Terminal Block 1, Terminal 1 is on the RIGHT,
Terminal Block 2, Terminal 1 is on the LEFT.

U1

+

+

-

-

1

1

TB1

TB2

JU5

JU6

JU16

JU7

JU3

JU2

JU15

JU8

Advertising