Appendix b - ranges – West Control Solutions MRC 9000 User Manual

Page 294

Advertising
background image

Edition 3

Rev G

Appendix B

B-1

Appendix B - Ranges

THERMOCOUPLE

JU7/JU8 POSITION

TYPE

OPERATING RANGE

Wide

J

-200

°

C to 760

°

C

-328

°

F to 1400

°

F

Narrow

J

-200

°

C to 450

°

C

-328

°

F to 842

°

F

Wide

K

-250

°

C to 1370

°

C

-418

°

F to 2498

°

F

Narrow

K

-250

°

C to 600

°

C

418

°

F to 1112

°

F

Wide

E

-250

°

C to 1000

°

C

-418

°

F to 1832

°

F

Narrow

E

-250

°

C to 350

°

C

-418

°

F to 663

°

F

Wide

N

-270

°

C to 1300

°

C

-441

°

F to 2373

°

F

Narrow

N

-270

°

C to 700

°

C

-441

°

F to 1292

°

F

Wide

G

0

°

C to 2300

°

C

32

°

F to 4172

°

F

Wide

C

0

°

C to 2300

°

C

32

°

F to 4172

°

F

Wide

D

0

°

C to 2300

°

C

32

°

F to 4172

°

F

Wide

NNM

0

°

C to 1400

°

C

32

°

F to 2552

°

F

Wide

PLII

0

°

C to 1400

°

C

32

°

F to 2552

°

F

Narrow

T

-250

°

C to 400

°

C

-421

°

F to 753

°

F

Narrow

R

*200

°

C to 1750

°

C

400

°

F to 3128

°

F

Narrow

S

*200

°

C to 1750

°

C

400

°

F to 3182

°

F

Narrow

B

*200

°

C to 1800

°

C

400

°

F to 3272

°

F

*Actual minimum of span is 0

°

C to prevent "LO" error condition during initial start-up at room ambient.

Advertising