Appendix B - Ranges
THERMOCOUPLE
JU7/JU8 POSITION
TYPE
OPERATING RANGE
Wide
J
-200
°
C to 760
°
C
-328
°
F to 1400
°
F
Narrow
J
-200
°
C to 450
°
C
-328
°
F to 842
°
F
Wide
K
-250
°
C to 1370
°
C
-418
°
F to 2498
°
F
Narrow
K
-250
°
C to 600
°
C
418
°
F to 1112
°
F
Wide
E
-250
°
C to 1000
°
C
-418
°
F to 1832
°
F
Narrow
E
-250
°
C to 350
°
C
-418
°
F to 663
°
F
Wide
N
-270
°
C to 1300
°
C
-441
°
F to 2373
°
F
Narrow
N
-270
°
C to 700
°
C
-441
°
F to 1292
°
F
Wide
G
0
°
C to 2300
°
C
32
°
F to 4172
°
F
Wide
C
0
°
C to 2300
°
C
32
°
F to 4172
°
F
Wide
D
0
°
C to 2300
°
C
32
°
F to 4172
°
F
Wide
NNM
0
°
C to 1400
°
C
32
°
F to 2552
°
F
Wide
PLII
0
°
C to 1400
°
C
32
°
F to 2552
°
F
Narrow
T
-250
°
C to 400
°
C
-421
°
F to 753
°
F
Narrow
R
*200
°
C to 1750
°
C
400
°
F to 3128
°
F
Narrow
S
*200
°
C to 1750
°
C
400
°
F to 3182
°
F
Narrow
B
*200
°
C to 1800
°
C
400
°
F to 3272
°
F
*Actual minimum of span is 0
°