Section 13

Edition 3
Rev G

13-34

6. Press the

to advance to the next parameter, OUTPUT 1 SHIFT.

Cx OUT 1 SHIFT

0 units

Note: Units correspond to Units
configured in Process Variables.

Selections

0 to 999999

(decimal position=0)

0 to 9.9999

(decimal position=4)

7. Press the

to advance to the next parameter, OUTPUT 2 SHIFT (only if Output 2 is used).

Cx OUT 2 SHIFT

0 units

Note: Units correspond to Units
configured in Process Variables.

Selections

0 to 999999

(decimal position=0)

0 to 9.9999

(decimal position=4)

OUTPUT SHIFT represents an offset of the on-off actuation points or proportional band relative to the normal

position. For example, if two on-off outputs are being used, one for heating and one for cooling, and a deadband

of 2

is desired between the two, set OUT 1 SHIFT to -1 and set OUT 2 SHIFT to +1.