West Control Solutions MRC 9000 User Manual

Page 313

Advertising
background image

Edition 3

Rev G

Appendix D

D-3

EXAMPLE 4

Operator Messages
Operator Messages are user defined messages to advise, or provide information, via the display, that selected
actuators are active. The messages are displayed as specified by the Operator Message Display Mode parameter
setting.

Application:
A user would like a visual indication whenever the total exceeds the preset along with instructions for an operator.

Configuration:
Operator Message:
Operator Message

1

OM1 Actuator

PRESET 1

OM1 Line 1 Text

TOTAL EXCEED PRESET

OM1 Line 2 Text

PHONE 908 6666

OM1 DISPLAY Mode*

PREEMPT TO OFF

*PREEMPT TO OFF - Specifies that the message overrides the display of values until any key is pressed, after
which it will not appear until the actuator goes inactive then active again.

EXAMPLE 5

Chart Messages
Chart Messages allow user defined text, up to 4 values, and a time/date stamp to be recorded on the chart,
triggered on the transition of an actuator, not its state. The message can be one to six lines with missing lines
causing the remaining line to be moved up. The message is recorded on the six outermost "lines" within the trend
area. Trend and time lines will not be overwritten or lost.

Since it may take considerable time for the instrument to record a message, three messages will be queued with a
fourth queue providing a QUEUE OVERFLOW message. All messages actuated while the queue is full are lost.

Application:
A user would like to print a message indicating that Alarm 1 on Process Value 2 has tripped.

Configuration:
Chart Message:
Chart Message

2

CM2 Actuator

A21 (Alarm 1 Process Value 2)

CM2 Message Text

ALARM 1 PRESSURE HI

CM2 Value 1

IV2 (Input Value for Pressure)

CM2 Value 2

PV2 (Process Value for Alarm)

CM2 Time/Date Stamp

YES

Operation:
During Normal Operation, if the pressure exceeds the alarm setpoint, the alarm (A21) will go on and at the same
time the actuator, A21, will trigger the chart message, ALARM 1 PRESSURE HI, and print the value of IV2, the
actual pressure, and PV2, the process value used to trigger the alarm.