Cx output slew rate 0% / min – West Control Solutions MRC 9000 User Manual

Page 239

Advertising
background image

Section 13

Edition 3
Rev G

13-8

12.Press the

to advance to the next parameter, OUTPUT SLEW RATE (only available with PID).

Cx OUTPUT SLEW RATE

0% / MIN

Selections

0 to100%

0 = OFF

SLEW RATE allows the control to slowly ramp the output to avoid a rapid start up. Abrupt changes may set the

outputs to 0%. If the slew rate is programmed to 60%/MIN, the rate of change would be 1%/second.

Press the

to change, then

or

to desired choice, then press the

.

Advertising