Ax4 alarm type off, Ax4 time base per sec – West Control Solutions MRC 9000 User Manual

Page 124

Advertising
background image

Section 4

Edition 3
Rev G

4-42

23. Press the

to advance to the next parameter, ALARM 4 TYPE.

* When CONTROL LOOP OPEN is selected for ALARM TYPE and NON PID is selected for CONTROL TYPE (CONTROLLERS section of

CONFIGURATION), prompt LOOP ALARM TYPE will be displayed

24. Press the to advance to the next parameter, ALARM 4 TIME BASE (only seen if Ax4 TYPE is RATE).

Press the

to change, then

to

desired choice, then press the

.

Press the

to change, then

,

to desired choice, then press

the

.

Ax4 TIME BASE

PER SEC

Selections

PER SEC PER MIN

PER HOUR PER DAY

P

R

O

C

E
S
S

V

A
R

I

A
B

L

E
S

Ax4 ALARM TYPE

OFF

Selections for recorder only

OFF

PROCESS - HIGH

PROCESS - LOW

RATE - RISING

RATE - FALLING

Additional selections for use

with controller option

BAND - WITHIN

BAND - OUTSIDE

DEVIATION - ABOVE

DEVIATION - BELOW

CONTROL LOOP OPEN*