Appendix d - examples – West Control Solutions MRC 9000 User Manual

Page 311

Advertising
background image

Edition 3

Rev G

Appendix D

D-1

Appendix D - Examples

EXAMPLE 1

Application:
Palmer-Bowlus Flume Height/Flow
Given: Transmitter output linear in distance (4mA=0.0", 20mA=2.85")

Configuration:
Inputs: As required
Custom Curves: See below
Derived Variables: See below
Process Variables (if alarming required): As required
Recorders: See below
Totalizers (if Totals required): As required
Instrument Settings: As required
LEDs/Relays: As required
Chart: As required

Custom Curves:
Custom Curves Number

1

CC1 Decimal Position of Input

2

CC1 Decimal Position of Output

2

CC1 Number of Points

20

CC1 Point Pair 1

0.00 --> 0.00

CC1 Point Pair 2

0.15 --> 0.30

CC1 Point Pair 3

0.30 --> 1.00

l
l

CC1 Point Pair 20

2.85 --> 50.20

Derived Variables:
DV Number

1

DV1 Display Tag

GPM

DV1 Function

Custom Curve 1

DV1 Input

IV1 (Input configured)

DV1 Display Units

Other

DV1 Units Description

CPM

DV1 Decimal Position

2

Recorders:
Recorder Number

1

R1 Recorder Tag

Flow

R1 Recording Method

Drag - Min to Max

R1 Value to Record

DV1

R1 Decimal Position

2

R1 Chart Divisions

100

R1 Zone 1 Low

Division 0

R1 Zone 1 High

Division 100

R1 Span 1 Low

0.00 GPM

R1 Span 1 High

50.20 GPM

R1 Scale Interval

10 Divisions