Edition 3
Rev G

5-2

Section 5

3. When this prompt is displayed with the AUTOMATIC/MANUAL choice, if the associated controller is configured

for PID control and is in the manual mode, pressing the DOWN key will display the prompts below:

Note: The controller may have its manual actuator set to something other than CAxFn, and in this case the

prompts below may be accessible even if the above section was AUTOMATIC.

Cx OUTPUT 1

visible if output 1 is proportional

MANUAL OUTPUT

nnn% value 0-100%, initially current value

Cx OUTPUT 2

visible if output 2 is proportional

MANUAL OUTPUT

nnn% value 0-100%, initially current value

These prompts allow the controller outputs to be manually changed. To change, press the key, then the

key as required to desired output %, then press the key. To exit, press the ke y.

4. Following the top level CONTROL STATE ACCESS prompts, if setpoint changes are enabled via ENABLES &

PASSWORDS and at least one setpoint has its PROMPT TEXT configured, the following prompt will appear:

SELECT

SETPOINTS

This prompt allows setpoint values to be changed. When displayed, pressing the key will display the

following prompt:

t t t t t t t t t t t t t t t t t t t t

default "SETPOINT x"

nnnnnnnn uuuuuu

This prompt is displayed for each setpoint which has its PROMPT TEXT configured, each prompt being accessed

via and keys. The "t t " field is the configured setpoint prompt text. The value for "nn" depends on

the setpoint's upper and lower limits decimal position. The "uu" field is the configured setpoint units text.