CONSTRUCTION (cont.)

Panel Cutout

12.7 inches wide x 12.7 inches high
(322.58mm wide x 322.58mm high)

Panel Depth

5.25 inches (133.35 mm)

Panel Protrusion

2.5 inches (63.5mm)

Weight

25 lbs maximum

ENVIRONMENTAL AND OPERATING CONDITIONS

Operating Temperature

0 to 50

°

C (32 to 122

°

F)

Storage Temperature

-40 to 65

°

C (-40 to 149

°

F)

Humidity

10 to 90% RH, non-condensing

Vibration

0.3 to 100 Hz @ 0.2g

Mounting Position

Up to 30

°

forward or backward tilt from vertical

Up to 10

°

side tilt from vertical

Reference Conditions

25

°

C

±

2

°

C and 60% RH

±

5% RH

OTHER SPECIFICATIONS

Clock Accuracy

1 minute/month typically, 4 minutes/month worst case

Battery Backup

5 years minimum life, 10 years typically

Simulated Variables

Four function generators

DIGITAL COMMUNICATIONS

Type

RS-232C/RS-485 serial communications port. Half-duplex.

Protocol

ModBus RTU

Network Control

Can be configured as either the master or a slave

Bit Rate

User configurable 1200, 2400, 4800, or 9600 bit per second

Parity

Odd, even or none

Address

User configurable 1 to 247

GENERAL REFERENCE DATA

Data Backup

EEPROM for input board calibration data
EEPROM for motherboard calibration data
Battery backed SRAM for configuration data

Warranty

Two years

APPROVALS AND COMPLIANCE

Safety

UL Approved for USA - UL 1092, UL 916, and QUXY - File E67237
UL Certified for Canada - CSA Spec 142 - File E67237

Immunity/Susceptibility

CE - Complies with EN 50082-1

Emissions

CE - Complies with EN 55011

Hazardous Locations

ETL Listed Class I and II, Division 2 and Class III, Division 1 and 2,
Reference No. 5604?2

* ModBus is a trademark of MODICON, Inc.