CURRENT OUTPUTS

Drivers

Any of over 20 values can be used to drive analog outputs (e.g. inputs, derived
variables, etc.)

Output Span

0 to 20mA or 4 to 20mA, nominal

Resolution

12 bits based on a 0 to 25.6mA span

Accuracy

±

0.1% of 20mA span reference accuracy

Compliance

650 ohm load

TOTALIZERS

Number

Four are included in the option

Digits

Nine, displayable with and without commas

Types

Continuous, preload count down, and pulse counting

Presets

One per totalizer

Pulsed Outputs

Fully configurable

COMPUTING CAPABILITIES

Derived Variables

Twelve

Math functions

Add, subtract, multiply, divide, average, exponential, log 10, log e, power 10, power e

Built-In Equations

Linear, polynomial, C to F, F to C, linear mass flow, DP mass flow, BTU, RH, Fo, ZrO

2

.

Other Functions

High select, low select, high peak, low peak, track and hold, 1 of 2 selector,
convert actuator

Custom Curves

Four 21 point curves, usable in multiple calculations

RH Calculation

Typically accurate to better than 1%
Clamps calculated value @ -10% and +110%

LOGIC CAPABILITIES

Actuators

Over 100 digital values are accessible

Derived Actuators

Twenty four combinations of 24 items

Logic Operators

NOT, OR, AND, parentheses

Timers

Four

Time/Date Combination Actuators

Six

POWER REQUIREMENTS

Line Voltage

Universal power supply, 85 min to 265 max. VAC 50/60Hz

Power Consumption

60 VA maximum

CONSTRUCTION

Enclosure

Gasketed cover, case, and windows. Structural foam case and cover with
plastic or glass window areas. Door lock available.

NEMA Rating

NEMA 3 standard, NEMA 4X optional

Conduit Openings

Four openings standard, 2 additional as required

Mounting

Panel, wall, or optional pipe mounting

Overall Dimensions

14.12 inches wide x 16.77 inches high x 7.75 inches deep
(358.65mm wide x 425.96mm high x 196.85mm deep)

(CONTINUED ON NEXT PAGE)