Section 13

Edition 3
Rev G

13-14

19.Press the

to advance to the next parameter, SECOND SETPOINT SOURCE (only if SECOND SP

ACTUATOR is not NONE/OFF).

Cx SECOND SP SOURCE

NONE USED

Selections

NONE USED

IV1 IV2 IV3 IV4
IV5 IV6 IV7 IV8

PV1 PV2 PV3 PV4

DV1 DV2 DV3
DV4 DV5 DV6
DV7 DV8 DV9

DV10 DV11 DV12

CV1 CV2 CV3 CV4
CV5 CV6 CV7 CV8

CV9 CV10 CV11 CV12

TOTAL 1 TOTAL 2
TOTAL 3 TOTAL 4

SP1 SP2 SP3 SP4
SP5 SP6 SP7 SP8

OUTPUT 11 OUTPUT 12
OUTPUT 21 OUTPUT 22
OUTPUT 31 OUTPUT 32
OUTPUT 41 OUTPUT 42

SV1 SV2 SV3 SV4

NOTE: Whatever value is selected
as the source of the setpoint, the
decimal position and the units type
follow what was configured in
Process Variables.

20.Press the

to advance to the next parameter, REMOTE SETPOINT RATIO.

NOTE: Ratio is applied to the remote
setpoint source before it is used, and
to the output of the first controller in
cascade mode before it is used as the
setpoint of the second controller.
Ratio is a multiplier applied to the
output. (Controller Output 1 *Ratio) =
Controller 2 Setpoint.

Cx REMOTE SP RATIO

1.000

Selections

.001 to 999.000

Press the

to change, then

,

to desired choice, then press the

.

Press the

to change, then

, to

desired number, then press the

.