Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual

Page 100

Advertising
background image

Startup

Chapter 6

6-11

!

ATTENTION: The following steps may cause motor rotation in
an unknown direction. To guard against equipment damage, always
disconnect the motor from the load before proceeding.

Function Settings

- Motor Connected

- NoĆLoad Condition

Important: The remaining steps are Function Settings that reference the
same parameters as grouped in Chapter 5 –– Operation and Programming.

Step 16

Stop the drive and remove and lock out all incoming power to the drive.

Remove the drive cover and reconnect the motor leads at terminals U

/

T1,

V

/

T2,

W

/

T3 at the Power Terminal Block.

Step 17

Replace the drive cover and tighten both thumbscrews. Apply power to the
drive and verify that no faults are displayed.

Both the main and mode displays should immediately light.

The main display should read

0000

. If the main display indicates

OU

or

LU

, an incorrect voltage is being applied to the drive.

The mode display should read

LL.

to allow control of the drive from the

Local Control and Programming Panel. If not, refer to Chapter 5 to
change Parameters 8 and 9 to local control.

Step 18 -- VoltsĆperĆHertz Curve Settings

Overload Protection Settings

Set Parameters 3 and 4 to match your volts-per-Hertz curve and drive
frequency range requirements as detailed in Chapter 5.

If overload protection is not required, leave Parameter 6 set to 0. If
overload protection is required:

Set Parameter 6 to correspond to the motor duty as outlined in Chapter 5.

Set Parameter 7 to correspond to the rated amps on your motor
nameplate.