Jog settings – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual
Page 74
Operation and Programming
Chapter 5
5-31
Jog Settings
Parameter
26
-- Jog Frequency
Units
= Hertz
Range
= 00.50/20.00
Factory Setting = 10.00
This parameter sets the jog frequency (speed) that the drive will use when
it receives either a local or remote jog command. Jog frequency may be set
in .01 Hz increments. Whenever the drive receives a jog command, Accel
Frequency Hold, Decel Frequency Hold, and Current Limit functions are
disabled.
Parameter
27
-- Jog Accel Time
Units
= Seconds
Range
= 0000/1600
Factory Setting = 00.50
This parameter sets the time it takes the drive to accelerate to the jog
frequency set in Parameter 26. If set to 0000, the drive will enter 40 ms but
display 0000.
From 000.1-1000 seconds, sets the Jog Accel Time in 0.1 second
increments.
From 1000-1600 seconds, sets the Jog Accel Time in 1 second increments.
Parameter
28
-- Jog Decel Time
Units
= Seconds
Range
= 0000/1600
Factory Setting = 00.50
This parameter sets the time it takes the drive to decelerate to 0. If set to
0000, the drive will enter 40 ms but display 0000.
From 000.1-1000 seconds, sets the Jog Decel Time in 0.1 second
increments.
From 1000-1600 seconds, sets the Jog Decel Time in 1 second increments.