Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual

Page 120

Advertising
background image

Preventive Maintenance and
Troubleshooting Common Drive Problems

Appendix B

B-13

5. The drive will not rampĆtoĆstop -- No fault is displayed.

Is Parameter 11 Stop Select set to rampĆtoĆstop?

Set Parameter 11 to 0.

Yes

Does Parameter 59 show an OU fault stored?

Yes

The drive is tripping on overvoltage during decel. Refer to page BĆ3.

No

No

Is the DC Hold Frequency set to high -- Is parameter 12 set to 00.50 Hz?

No

Set Parameter 12 to 00.50 Hz.

Yes

Is Parameter 18 Decel Frequency Hold on -- Does the motor have an

overhauling load?

Yes

No

If Parameter 18 Decel Frequency Hold is set to 1 (On), an overhauling load

may cause the decel ramp to hold at one frequency for an extended period.

This may cause rampĆtoĆstop commands to appear to be nonĆfunctional.

Contact your nearest AĆB representative for application assistance.