Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual

Page 114

Advertising
background image

Preventive Maintenance and
Troubleshooting Common Drive Problems

Appendix B

B-7

Auxiliary Interlock

DC Bus Neon Light

Drive Nameplate

Control and Signal Wiring Terminal Block

Power Terminal Block

Lock Switch

Figure BĆ2 -- 7Ă1/2Ć20ĂHP (5.5Ć15kW)

1. The motor will not run --

OH

is displayed.

Is ambient temperature above the rated limit of 505C? Are the cooling fins

clogged or is the heat sink dirty? For 7Ă1/2Ć20ĂHP (5.5Ć15ĂkW) units, is the

cooling fan rotating?

Lower the ambient temperature, clean the heat sink, or replace the cooling

fan.

No

Yes

Contact your nearest AĆB representative for application assistance.

Advertising