Bulletin 1333 Options

Using Bulletin 1332 and

Bulletin 1332 and 1333 Options can be used with Series D drives.

1333 Options with

Point-to-point interconnections and the required Series D parameter

Bulletin 1333 Series D Drives

settings are detailed below and on the following pages. Refer to the
individual option kit instructions for installation procedures and the
additional information required to setup each option.

Bulletin 1333 Series D

Control and Signal Wiring Terminal Block

1332ĆMODĆF

Remote Operator Station

1332ĆMODĆF

Remote Operator Station

Term 3

Term 10

Term 11

Term 3

Term 4

Term 5

Term 7

Term 8

Term 9

Term 11

Term 12

Term 13

Term 1

Term 2

Term 3

Term 7

Term 8

Term 6

Start/Stop and Forward/Reverse Control

To allow the 1333 Series D to accept 1332-MOD-F start/stop and
forward/reverse commands, Parameter 8 Local/Remote Control Enable
must be set to 1 or 3.

Speed Control

To allow the 1333 Series D to accept the 1332-MOD-F speed
potentiometer signal, Parameter 9 Local/Remote Speed Enable must be set
to 1, 2 or 3.