If you use faa or gaa units, Caution, Power terminal block cover) – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual

Page 34

Advertising
background image

Installation and Wiring

Chapter 4

4-17

If You Use

FAA or GAA Units

Lugs are required to terminate wires for FAA or GAA units at the Power Terminal Block.

Power

Recommended

Rating

Wire

Wire

Code

Group ❶

Size

FAA

2

6 AWG (16.0mm

2

)

GAA

2

3 AWG (30.0mm

2

)

Wire group number chart, page 4Ć6.

UL Listed crimp connectors are required and must be installed using the proper crimping tool.
Crimp connectors must be sized to the wire size chosed.
When using crimp connectors on terminal studs that are not isolated from each other,

a minimum spacing of 0.4 Inches (10.16Ămm) is required.

(Power Terminal Block Cover)

CAUTION :

230/208VA.C.

Input Voltage Only

Use 75 Degree C ❷ AWG Copper Wire

Use U.L. Listed Crimp Connectors ❸

Select from the following drive input fuses.

Drive Rating FAA Fuse Size 100AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating GAA Fuse Size 125AFuse Type 600V Class K5 UL Listed or Equivalent