Parameter, Tb15 preset/reset – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual

Page 68

Advertising
background image

Operation and Programming

Chapter 5

5-25

Parameter

20

-- TB15 Preset/Reset

Units

= Code

Range

= 0/1

Factory Setting = 0

This parameter selects the control function of switch S3 when three
external switches are connected to the Control and Signal Wiring Terminal
Block.

Parameter 20 settings.

When set to 0, external switches S1, S2 and S3 connected to the Control
and Signal Wiring Terminal Block can be used to select Preset Frequencies
2-8 and Accel/Decel Times 2-4.

When set to 1, external switches S1 and S2 connected to the Control and
Signal Wiring Terminal Block can be used to select Preset Frequencies 2-4
and Accel/Decel Times 2-4. If a third switch is installed, switch S3 is used
to remotely reset the drive should a drive fault occur.

As shown in Figure 4-5 in Chapter 4 ––

If Parameter 19 = 2

When

and

and

Control Board External

External

Switch SW2

Switch S1 Switch S2

is Set to

is Set to

is Set to

The Parameters Selected are

4SP

OFF

OFF

None

4SP

ON

OFF

Preset Frequency 2 + Accel Time 2 + Decel Time 2

4SP

OFF

ON

Preset Frequency 3 + Accel Time 3 + Decel Time 3

4SP

ON

ON

Preset Frequency 4 + Accel Time 4 + Decel Time 4

If Parameter 19 = 1

When

and

and

Control Board External

External

Switch SW2

Switch S1 Switch S2

is Set to

is Set to

is Set to

The Parameters Selected are

4SP

OFF

OFF

None

4SP

ON

OFF

Accel Time 2 + Decel Time 2

4SP

OFF

ON

Accel Time 3 + Decel Time 3

4SP

ON

ON

Accel Time 4 + Decel Time 4

If Parameter 19 = 0

When

and

and

Control Board External

External

Switch SW2

Switch S1 Switch S2

is Set to

is Set to

is Set to

The Parameters Selected are

4SP

OFF

OFF

None

4SP

ON

OFF

Preset Frequency 2

4SP

OFF

ON

Preset Frequency 3

4SP

ON

ON

Preset Frequency 4