Output meter settings, Monitoring mode settings – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual

Page 88

Advertising
background image

Operation and Programming

Chapter 5

5-45

Output Meter Settings

Parameter

55

-- Frequency Output (Amps)

Units

= % of Maximum Output Signal

Range

= 075/125

Factory Setting =

100

This parameter is used to calibrate an output frequency ammeter while the
drive is running. It may be set from 75-125% of the maximum output
signal, 1 mA. The 1 mA signal is selected by setting switch SW1 on the
Control Board to the 1 mA position.

Parameter

56

-- Frequency Output (Volts)

Units

= % of Maximum Output Signal

Range

= 075/125

Factory Setting =

100

This parameter is used to calibrate an output frequency voltmeter while the
drive is running. It may be set from 75-125% of the maximum output
signal, 10V DC. The 10V DC signal is selected by setting switch SW1 on
the Control Board to the 10V DC position.

Monitoring Mode Settings

Parameter

57

-- Monitor Display Select

Units

= Code

Range

= 0/1/2

Factory Setting = 0

This parameter sets one of three alternate monitoring modes that may be
selected while the drive is running.

When set to 0,

A0

–– monitor equivalent drive output current.

When set to 1,

A1

–– monitor equivalent motor RPM.

When set to 2,

A2

–– monitor drive control frequency.

Parameter

58

-- Motor Pole Select

Units

= Code

Range

= 2/4/6/8/10

Factory Setting = 4

To allow motor RPM to be calculated and displayed when monitoring

mode

A1

is selected, this parameter is used to enter the number of motor

poles.