Startup

Chapter 6

6-12

Function Settings

Step 19

- Motor Connected

Press the shift pushbutton once and

LJ.

will be shown in the mode display.

- NoĆLoad Condition

Press and release the directional start pushbutton that will be your forward
motor direction. If the direction of motor rotation is incorrect:

Remove input power, wait until the displays are no longer lit, then
remove the drive cover.

Verify that the DC bus neon light is no longer lit and that bus voltage at
the +Bus and –Bus terminals of the power terminal block is zero.

Interchange any two of the three motor leads at terminals U

/

T1,

V

/

T2,

W

/

T3 at the Power Terminal Block.

Replace the drive cover and tighten both thumbscrews. Apply power to
the drive and verify that no faults are displayed.

Step 20 -- Output Meter Settings

If an external output ammeter or voltmeter is connected to the Control and
Signal Wiring terminal block, the meter should be calibrated and switch
SW1 should be set as detailed by Parameters 55 or 56 in Chapter 5.