Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual

Page 58

Advertising
background image

Operation and Programming

Chapter 5

5-15

An auxiliary interlock signal will stop the drive and display either

AU

or

AS

as programmed by Parameter 21.

If set to 2, local control has been selected, but a maintained stop command
or jumper must also be present at terminals 8 and 9 of the Control and
Signal Wiring Terminal Block. If not present, all of the following

commands will generate an

OP

error. An

L

will be the left-hand letter

shown in the Mode Display.

Both directional start pushbuttons on the Local Control and
Programming Panel will be functional.

Local jog can be selected by pressing the Shift button.

If Parameter 10 Reverse Lockout is on, only one directional start
pushbutton will be available for jogging or running the drive.

The local stop button will stop the drive as programmed by Parameters
11-14.

An auxiliary interlock signal will stop the drive and display either

AU

or

AS

as programmed by Parameter 21.

An external stop signal at terminals 8 and 9 of the Control and Signal
Wiring Terminal Block will allow the drive to coast-to-stop but display

an

OP

error.

If set to 3, external 3-wire control has been selected. An

E

will be the

left-hand letter shown in the Mode Display.

Drive start, jog and forward/reverse is controlled externally through the
Control and Signal Wiring Terminal block. Neither directional start
pushbutton on the Local Control and Programming Panel will be
functional and local jog cannot be selected.

An external jog signal will jog the drive and display

EJ

. Local jog

cannot be selected.

If Parameter 10 Reverse Lockout is on, only one direction is available
for jogging or running the drive.

The local stop button will allow the drive to coast-to-stop and display

OP

.

An auxiliary interlock signal will stop the drive and display either

AU

or

AS

as programmed by Parameter 21.