Installation and Wiring

Chapter 4

4-23

Terminals 7 and 8
Start

This remote input will command the drive to start if all hardwired
interlocks are closed and Parameter 8 is set to 1 or 3. The drive will
continue to run until a stop command is received, an interlock is opened,
or a fault is detected.

Important: As shown in Figure 4-4, for external two wire start/stop
control, terminals 7 and 8 must be jumpered.

Terminals 9 and 8
Stop

This remote input will command the drive to stop if Parameter 8 is set to 1
or 3. The drive will then either ramp-to-stop or coast-to-stop as selected by
Parameter 11.

Important: If ramp-to-stop is selected, refer to Parameters 11 and 18 if
the drive will be subjected to an overhauling load. If Parameter 18 Decel
Frequency Hold is set to 1 (On), an overhauling load may cause the decel
ramp to hold at one frequency for an extended period, causing ramp-to-stop
commands to appear to be non-functional.

Terminals 10 and 8
Reverse

This remote input will command the drive to reverse direction if Parameter
8 is set to 1 or 3 and Parameter 10 is set to 0. Both the local and remote
reverse will be locked out if Parameter 10 is set to 1.

Terminals 12 and 11
Jog

This remote input will jog the drive if Parameter 8 is set to 1 or 3. When
jogged:

–– The drive will jog to the frequency range set by Parameter 26

–– Within the accel time set by Parameter 27

–– In the direction determined by Parameter 10.

When the jog pushbutton is released, the drive will decelerate within the
time set by Parameter 28.