Chapter 5

5-14

Local/Remote Control Enable

Important: If the Remote Operator Station option is installed, Parameter 8
must be set to 1 or 3 to allow remote control.

Parameter 08 -- Local/Remote Control
Units

= Code

Range

= 0/1/2/3

Factory Setting = 0

This parameter enables or disables the drive start, jog, and forward/reverse
functions as follows. The stop button on the Local Control and

Programming Panel will always be functional, but may generate an

OP

error for certain settings detailed below. If installed at the Control and
Signal Wiring Terminal Block, auxiliary input switches S1, S2 and/or S3
will always function as programmed by Parameters 19 and 20 when a valid
start command is present.

If set to 0, local control has been selected. An

L

will be the left-hand letter

shown in the Mode Display. A maintained start command or jumper is not
required at terminals 7 and 8 of the Control and Signal Wiring Terminal
Block.

Both directional start pushbuttons on the Local Control and
Programming Panel will be functional.

Local jog can be selected by pressing the Shift button.

If Parameter 10 Reverse Lockout is on, only one directional start
pushbutton will be available for jogging or running the drive.

The local stop button will stop the drive as programmed by Parameters
11-14.

An auxiliary interlock signal will stop the drive and display either

AU

or

AS

as programmed by Parameter 21.

If set to 1, external 2-wire control has been selected. An

E

will be the

left-hand letter shown in the Mode Display.

Drive start, jog and forward/reverse is controlled externally through the
Control and Signal Wiring Terminal block. Neither directional start
pushbutton on the Local Control and Programming Panel will be
functional.

An external jog signal will jog the drive and display

EJ

. Local jog

cannot be selected.

If Parameter 10 Reverse Lockout is on, only one direction is available
for jogging or running the drive.

The local stop button will allow the drive to coast-to-stop and display

OP

.