Installation and wiring chapter 4 – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual

Page 37

Advertising
background image

Installation and Wiring

Chapter 4

4-20

Figure 4Ć5 -- Control and Signal Wiring Terminal Block Interconnection Diagram

Pot

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

Wiper

Pot

High

Pot

Low

External

Speed Pot

+

-

+

-

+

-

CR1

CR2

CR3

CR3

Analog Meter

4-20mA

CR1

CR3

CR3

CR2

Fault Contacts

Drive

19

20

21

22

23

24

Start

Stop

Start/Stop

3ĆWire Control

2ĆWire Control

Rev

Jog

S1

S2

Reset

Lockout

Aux

Interlock

1mA

Logic

Common

S1

S2

S3

1mA Maximum when SW1 set to 1mA

SW2 set to 4SP

SW2 set to 8SP

0Ć5ĂV

0Ć10ĂV

10V

4SP

8SP

SW1

SW2

Programmable Outputs

End

Shield

Factory

Installed

Jumper

10V Maximum when SW1 set to 10V

Earth

Ground

Drive Input Power Applied

No Output Signal Present

Drive Input Power Applied

No Fault Present

Stop

Start

Factory

Set to

4SP

Output Signal

Recommended

Recommended

Terminals

Output Signal

Wire Group ❶

Wire Size

Torque

Terminal 6 and Logic Common

0Ć1mA or 0Ć10V Meter

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 19 and I20

CR1 Programmable Contact

3

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 20 and 21

CR2 Programmable Contact

3

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 22 and 23

CR3 Fault Contact

3

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 23 and 24

CR3 Fault Contact

3

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Wire group number chart, page 4Ć6.

Input Signal

Recommended

Recommended

Terminals

Input Signal

Wire Group ❶

Wire Size

Torque

Terminals 1, 2, 3

External Speed Potentiometer

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 3, 8, 11 and 17

Logic Common

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 4 and 3

0Ć5 or 0Ć10V DC

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 5 and 3

4Ć20mA

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 7 and 8

Start

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 9 and 8

Stop

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 10 and 11

Reverse

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 12 and 11

Jog

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 13 and 14

S1/4SP Position

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 14 and 15

S2/4SP Position

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 11 and 13

S1/8SP Position

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 11 and 14

S2/8SP Position

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 11 and 15

S3/8SP Position

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 16 and 17

Auxiliary Interlock

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Terminals 17 and 18

Reset Lockout

5

16 AWG (1.5mm

2

) 7 InĆLbs (.791 NĆm)

Advertising