Operation and Programming

Chapter 5

5-42

Lower and Upper Frequency Clamp Settings

➊ Maximum Output Frequency

100% of Input Frequency Signal

0%

0

Parameter 50

Minimimum Frequency = 0.5

Parameter 51

n

o

it

a

r

e

l

e

c

c

A

➊ Maximum Output Frequency = 50 Hz if Parameter 3 = 50
60 Hz if Parameter 3 = 60
Parameter 15 if Parameter 3 = FF

➊ Maximum Output Frequency

100% of Input Frequency Signal

0%

0

Parameter 50

Parameter 51

n

o

it

a

r

e

l

e

c

e

D

Minimimum Frequency = 0.5

Parameter

51

-- Upper Frequency Clamp

Units

= Hertz

Range

= 00.50/400.0

Factory Setting = 400.0

This parameter sets the highest frequency or speed that the drive can be set
to by any input control signal, unless Parameter 15 (Maximum Frequency)
or Parameter 3 (Frequency Range) has been set lower. If set to a value
higher than Parameter 3 or 15, the value will be entered, but the drive will
default to the lowest value set by Parameter 3 or 15 when operating.

From 00.50-100.0 Hz, Parameter 51 sets the Upper Frequency Clamp in
.01 Hz increments.

From 100.0-400.0 Hz, Parameter 51 sets the Upper Frequency Clamp in
0.1 Hz increments.