Lower and upper frequency clamp settings – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual

Page 84

Advertising
background image

Operation and Programming

Chapter 5

5-41

Lower and Upper

Important: The maximum allowable drive output frequency will be

Frequency Clamp Settings

determined by the lowest value programmed into the following parameters:

Parameter 3 Frequency Range

Parameter 15 Maximum Frequency

Parameter 51 Upper Frequency Clamp

Parameter 53 Bias Frequency –– If Parameter 53 is Higher Than
Parameter 54

Parameter 54 Gain Frequency –– If Parameter 54 is Higher Than
Parameter 53

Parameter

50

-- Lower Frequency Clamp

Units

= Hertz

Range

= 00.50/400.0

Factory Setting = 00.50

This parameter sets the minimum frequency or speed that the drive can be
set to by any input control signal.

From 00.50-100.0 Hz, Parameter 50 sets the Lower Frequency Clamp in
.01 Hz increments.

From 100.0-400.0 Hz, Parameter 50 sets the Lower Frequency Clamp in
0.1 Hz increments.

Important: If an external potentiometer, a 0-5V DC, a 0-10V DC or a
4-20mA frequency reference is required:

For directly proportional applications, enable Parameter 52 and enter a
minimum value of 00.50 for Parameter 53 if the Lower Frequency
Clamp is to set the minimum frequency.

For inverse follower applications, enable Parameter 52 and enter a
minimum value of 00.50 for Parameter 54 if the Lower Frequency
Clamp is to set the minimum frequency.

Advertising