Parameter, Bias frequency, Gain frequency – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual
Page 87
Operation and Programming
Chapter 5
5-44
Bias and Gain Settings
➊ 100% of Output Frequency
100% of Input Frequency Signal
0%
Parameter 53 = 0%
Ac
celeratio
n
When Bias Frequency
is Less Than Gain
a Directly Proportional
Input Frequency Signal
is Produced
Bias Frequency Less Than Gain
Parameter 54
➊ 100% of Output Frequency = 50 Hz if Parameter 3 = 50
60 Hz if Parameter 3 = 60
Paramer 15 if Parameter 3 = FF
➊ 100% of Output Frequency
100% of Input Frequency Signal
Bias Frequency Greater Than Gain
0%
0%
Parameter 53
n
o
it
a
r
e
l
e
c
e
D
When Bias Frequency
is Greater Than Gain
an Inversely Proportional
Input Frequency Signal
is Produced
Parameter 54
Parameter
53
-- Bias Frequency
Units
= Hertz
Range
= 00.00/400.0
Factory Setting = 00.00
From 00.50-400.0 Hz, Parameter 53 sets the Bias Frequency in .01 Hz
increments.
From 100.0-400.0 Hz, Parameter 53 sets the Bias Frequency in 0.1 Hz
increments.
Parameter
54
-- Gain Frequency
Units
= Hertz
Range
= 00.50/400.0
Factory Setting = 60.00
From 00.50-400.0 Hz, Parameter 54 sets the Gain Frequency in .01 Hz
increments.
From 100.0-400.0 Hz, Parameter 54 sets the Gain Frequency in 0.1 Hz
increments.