Preventive Maintenance and
Troubleshooting Common Drive Problems

Appendix B

B-12

3. The motor generates an excessive amount of heat -- No fault is displayed.

Is full load demanded continuously at low frequency?

An OL trip occurs when the load current is greater than 140% for one minute.

Lighten the load or resize the drive and motor to meet your application.

Yes

Is the motor operating above the full load current?

No

The load is beyond the motor capacity. Check the mechanical installation. If

the motor and drive are undersized, resize them for your application.

Yes

No

Check the motor and wiring connections for an open phase condition.

4. The drive will not reverse in local control -- No fault is displayed.

Yes

No

Has the drive been programmed to lockout reverse operation (Parameter 10

set to 1)?

Set Parameter 10 to 0.

Contact your nearest AĆB representative for application assistance.