Operation and Programming

Chapter 5

5-19

DC Brake Settings

Parameters 12, 13 and 14 sets the DC braking action that will occur when
the drive is ramped-to-stop or programmed to change direction while the
drive is operating for both local and remote control. If DC braking is to be
used, Parameter 11 must be set to 0, ramp-to-stop.

DC Brake Settings

Ramp-to-Stop

DC Break

Drive Stopped

Parameter 12

Parameter 13

Parameter 14

Parameter

12

-- DC Hold Frequency

Units

= Hertz

Range

= 00.50/60.00

Factory Setting = 00.50
Parameter 12 sets the braking frequency of the internal DC brake in .01 Hz
increments.

Parameter

13

-- DC Hold Time

Units

= Seconds

Range

= 000/10.0

Factory Setting = 000
Parameter 13 will set the braking time of the internal DC brake when used
in conjunction with parameters 12 and 14. Parameter 13 will set the
hold-at-zero time for changes in direction or stop commands when
Parameter 14 is set to 0 (disabled). Parameter 13 may be programmed in
0.1 second increments.

Parameter

14

-- DC Hold Volts

Units

= Code

Range

= 0/10

Factory Setting = 0
If set to 0, the DC brake function will be disabled and Parameters 12 and
14 will have no effect on drive operation.

If set to a value of 1-10, the DC brake function will be enabled. Parameters
12 and 13 along with Parameter 14 will then set the DC brake function.
The value of Parameter 14 determines the level or strength of the braking
that occurs, with 1 being the lowest, 10 the highest.