Operation and Programming

Chapter 5

5-30

Parameter

24

-- CR1 Frequency

Units

= Hertz

Range

= 00.50/400.0

Factory Setting = 00.50

This parameter sets the frequency that will cause drive supplied contact
CR1 to close when Parameter 22 is set to 3.

From 00.50-100.0 Hz, this parameter sets the value of CR1 Frequency in
.01 Hz increments.

From 100.0-400.0 Hz, this parameter sets the value of CR1 Frequency in
.1 Hz increments.

Parameter

25

-- CR2 Frequency

Units

= Hertz

Range

= 00.50/400.0

Factory Setting = 00.50

This parameter sets the frequency that will cause drive supplied contact
CR2 to close when Parameter 23 is set to 3.

From 00.50-100.0 Hz, this parameter sets the value of CR2 Frequency in
.01 Hz increments.

From 100.0-400.0 Hz, this parameter sets the value of CR2 Frequency in
.1 Hz increments.