Operation and Programming
Chapter 5
5-30
Parameter
24
-- CR1 Frequency
Units
= Hertz
Range
= 00.50/400.0
Factory Setting = 00.50
This parameter sets the frequency that will cause drive supplied contact
CR1 to close when Parameter 22 is set to 3.
From 00.50-100.0 Hz, this parameter sets the value of CR1 Frequency in
.01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of CR1 Frequency in
.1 Hz increments.
Parameter
25
-- CR2 Frequency
Units
= Hertz
Range
= 00.50/400.0
Factory Setting = 00.50
This parameter sets the frequency that will cause drive supplied contact
CR2 to close when Parameter 23 is set to 3.
From 00.50-100.0 Hz, this parameter sets the value of CR2 Frequency in
.01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of CR2 Frequency in
.1 Hz increments.