Startup

Chapter 6

6-14

Final Settings

Step 24

- Motor Connected

If Heavy Duty Dynamic Braking is to be Installed

- Load Connected

If Heavy Duty Dynamic braking is required, set Parameters 11 and 14 to 0.

Step 25

If Machine Resonance is Encountered

Set Parameters 42-45 to skip those frequencies which cause the machine to
resonate.

Step 26

If Nuisance Tripping is Encountered

Enable Parameters 17 and/or 18 to disable drive acceleration or
deceleration during high Bus current or voltage conditions.

Step 27

If the Connected Load is an Overhauling Load

Set Parameter 18 to 0 to disable Decel Frequency Hold.

Step 28

If a Different Running Monitor Mode is Required

Change Parameter 57 to:

0 to monitor drive output current.

1 to monitor equivalent motor RPM.

2 to monitor drive control frequency.

Step 29

If an External 2 or 3-Wire Control Scheme is to be Used

Connect the 2 or 3-wire controls as shown in Figure 4-3 and described in
Chapter 4.

Set Parameter 8 to 1 for 2-wire control, 3 for 3-wire control.

Repeat the startup procedure starting from step 1.