Preventive Maintenance and
Troubleshooting Common Drive Problems

Appendix B

B-10

2. The motor will not run continuously --

OC

is displayed.

Does a short circuit exist in the output leads or motor windings?

Remove the cause of the short circuit.

Yes

Does a ground fault exist between the drive output leads and the motor or in

the motor windings?

No

Remove the cause of the ground fault.

Is the application a fan or pump system?

Does the drive trip when the speed reference is below 5.0Hz?

Is the acceleration time too short? Is Parameter 17, Accel Frequency Hold

off?

Is the load within the rated current of the drive?

No

No

No

Yes

Yes

Yes

No

Reduce the boost setting

in Parameter 5.

Yes

Change the V/Hz ramp to

variable by setting

Parameter 4 to 1, then

reduce the boost level

setting in Parameter 5 if

required.

Increase the value of Accel Time 1 Parameter 1, or set Parameter 17 Accel

Frequency Hold on.

No

Program Parameter 46 Current Limit to eliminate nuisance tripping, lighten

the load, or resize the drive and motor to meet your application.

Is OC displayed even if the drive output leads are disconnected?

No

Verify motor operation by line operating the motor or repeating the above. Is

the motor now operating correctly?

No

Contact your nearest AĆB representative for application assistance.

Yes

Yes

Yes