Step 15a -- Preset Frequency and Aux Accel/Decel Enable Check

If external switches have been connected to the Control and Signal Wiring
Terminal Block as detailed in Chapter 5, preset frequencies as well as
auxiliary accel and decel times can be checked.

Step 15b -- Preset Frequency and Aux Accel/Decel Enable Check

Enable Auxiliary Accel/Decel Settings

Stop the drive and depress the lock button to allow programming. Set
Parameter 19 to 2. By setting Parameter 19 to 2, auxiliary accel/decel times
will be enabled and can be checked simultaneously with preset speeds.

Step 15c -- Preset Frequency and Aux Accel/Decel Enable Check

If two preset speed switches have been installed, verify that switch
SW2 is set to 4SP.

Closing switch S1 and opening switch S2 will force the drive to

20.00 Hz, the Preset Frequency 2 value set by Parameter 29, within the
2nd auxiliary accel time set by Parameter 36, or the 2nd auxiliary decel
time set by Parameter 37.

Opening switch S1 and closing switch S2 will force the drive to
30.00 Hz, the Preset Frequency 3 value set by Parameter 30, within the
3rd auxiliary accel time set by Parameter 38, or the 3rd auxiliary decel
time set by Parameter 39.

Closing switches S1 and S2 will force the drive to 40.00 Hz, the Preset
Frequency 4 value set by Parameter 31, within the 4th auxiliary accel
time set by Parameter 40, or the 4th auxiliary decel time set by
Parameter 41.