Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual

Page 99

Advertising
background image

Startup

Chapter 6

6-10

Function Checks

Step 15d -- Preset Frequency and Aux Accel/Decel Enable Check

- Motor Disconnected

If three preset speed switches have been installed, verify that switch
SW2 is set to 8SP.

Closing switch S1 and opening switches S2 and S3 will force the drive
to 20.00 Hz, the Preset Frequency 2 value set by Parameter 29, within
the 2nd auxiliary accel time set by Parameter 36, or the 2nd auxiliary
decel time set by Parameter 37.

Opening switches S1 and S3 and closing switch S2 will force the drive
to 30.00 Hz, the Preset Frequency 3 value set by Parameter 30, within
the 3rd auxiliary accel time set by Parameter 38, or the 3rd auxiliary
decel time set by Parameter 39.

Closing switches S1 and S2 and opening switch S3 will force the drive
to 40.00 Hz, the Preset Frequency 4 value set by Parameter 31, within
the 4th auxiliary accel time set by Parameter 40, or the 4th auxiliary
decel time set by Parameter 41.

Opening switches S1 and S2 and closing switch S3 will force the drive
to 15.00 Hz, the Preset Frequency 5 value set by Parameter 32, within
the 4th auxiliary accel time set by Parameter 40, or the 4th auxiliary
decel time set by Parameter 41.

Opening switch S2 and closing switches S1 and S3 will force the drive
to 25.00 Hz, the Preset Frequency 6 value set by Parameter 33, within
the 4th auxiliary accel time set by Parameter 40, or the 4th auxiliary
decel time set by Parameter 41.

Opening switch S2 and closing switches S1 and S3 will force the drive
to 35.00 Hz, the Preset Frequency 7 value set by Parameter 34, within
the 4th auxiliary accel time set by Parameter 40, or the 4th auxiliary
decel time set by Parameter 41.

Closing switches S1, S2 and S3 will force the drive to 45.00 Hz, the
Preset Frequency 8 value set by Parameter 35, within the 4th auxiliary
accel time set by Parameter 40, or the 4th auxiliary decel time set by
Parameter 41.