Operation and Programming

Chapter 5

5-9

Parameter

02

-- Deceleration Time 1

Units

= Seconds

Range

= 0000 to 1600

Factory Setting = 005.0

Important: Parameter 11 must be set to 0 to allow the drive to
ramp-to-stop

This parameter determines the time that it will take the drive to decelerate
and ramp-to-stop over a 60 Hz change in frequency. From 0.5 to 0 Hz, the
accel rate is non-linear and set by either DC injection braking or the DC
dynamic brake if it is installed. From maximum output frequency to 0.5
Hz, the accel rate set by Parameter 2 will remain constant. The total time it
will take the drive to decelerate from maximum drive output frequency to
0.5 Hz is:
Total time = (Maximum Drive Output Frequency

×

Parameter 2)

÷

60.

If set to 0000, the drive will enter 40 ms but display 0000.

From 00.10-1000 seconds, this parameter sets the decel time value in 0.1
second increments.

From 1000-1600 seconds, this parameter sets the decel time value in 1
second increments.

Decel Settings

0

0.5

60 Hz

Output Frequency

50 Hz

Parameter 3 = 50Hz

Time

40mS

Parameter 2

n

o

it

a

r

e

l

e

c

e

D

➊ DC injection braking or DC dynamic braking (if installed).

0

0.5

60 Hz

Output Frequency

50 Hz

Parameter 3 = 60Hz

Time

40mS

Parameter 2

n

o

it

a

r

e

l

e

c

e

D

Parameter 3 = FF
Parameter 15 = 120Hz

0

0.5

60 Hz

Output Frequency

50 Hz

Time

40mS