Preventive Maintenance and
Troubleshooting Common Drive Problems

Appendix B

B-11

2. The motor will not run continuously --

OL

is displayed.

Is the load current equal to the motor nameplate rating? Is the load current
within the rated current of the

drive?

An OL trip occurs when the load current is greater than 140% for one minute.

Lighten the load or resize the drive and motor to meet your application.

No

Is Parameter 6 set to 1, 2 or 3?

Yes

When set to 1, 2 or 3, the thermal overload function is enabled. Check for the

correct setting as detailed in Chapter 5.

No

Yes

Yes

No

Is Parameter 7 set to the rated motor nameplate value?

An OL trip occurs when the load current is greater than 125% of the overload

current value set in Parameter 7 for one minute. Lighten the load or resize the

drive and motor to meet your application.

Set Parameter 7 to the rated motor nameplate value.

2. The motor will not run continuously --

OU

is displayed.

Is the incoming AC power line high?

Monitor and correct the AC line.

No

Yes

No

Is an overhauling load present -- Does the load increase the motor speed

beyond the drive set speed?

Yes

Is the deceleration time too short? Is Parameter 18, the Decel Frequency

Hold off?

Increase the value of Decel Time 1 Parameter 2, or set Parameter 18 Decel

Frequency Hold on.

Yes

Increase the value of Parameter 14 DC Hold Volts. Install the Heavy Duty

Dynamic Brake Option. Does the problem still exist?

No

Contact your nearest AĆB representative for application assistance.

Yes